Roofing Q&A

Do I need ridge vent, soffit vent, or both?

TL;DR — Use both: continuous soffit intake + continuous ridge exhaust.
Size by net-free area (NFA) (typ. 1:300 of attic floor area), target 40–60% intake at soffits and 40–60% exhaust at ridge. Don’t mix too many exhaust types and never rely on ridge vent without soffit intake.

Why both soffit + ridge?#

A passive system needs low intake and high exhaust to create stack effect and wind-assisted flow. With only ridge vent you depressurize the house and pull conditioned air from below; with only soffit you trap heat and moisture.

Common short-circuits

  • Box/power fans + ridge together (stronger fan pulls from ridge instead of soffits).
  • Hip roofs with tiny ridges (exhaust area too small for the attic size).
  • Painted-over or perforated vinyl soffits with solid sheathing behind them.

Quick sizing (NFA)#

  1. Measure attic floor area (length × width in ft²).
  2. Start with 1:300: area ÷ 300 = total NFA (in²).
  3. Split 50/50 (or 60/40 intake/exhaust when you have long eaves).
  4. Convert product ratings:
    • If your ridge vent is 18 in²/ft, and ridge length is 40 ft → 18 × 40 = 720 in² exhaust.
    • If soffit strip vent is 10 in²/ft with two eaves totaling 60 ft → 10 × 60 = 600 in² intake. Add baffles or more intake to reach balance.

Pro tip: NFA is net area of free openings, not the slot cut. Always use the manufacturer’s NFA per foot.

Where ridge + soffit makes sense#

  • Steep-slope (≥ 3:12) roofs with continuous eave overhangs.
  • Attics that allow a clear air path from soffit to ridge (no fire blocks).
  • You can still use ridge on hip roofs, but you may need hip vents or additional high vents to meet the exhaust NFA.

When it fails (and fixes)#

  • No soffit intake → add intake (continuous strip or individual vents) and install baffles above insulation.
  • Slots bridged by underlayment at ridge → re-cut/clear slot; verify the vent’s slot width requirement.
  • Mixed exhaust (box + power + ridge) → pick a single strategy and rebalance NFA.
  • Ice-dam/humid zones → add full-height baffles at eaves and air-seal penetrations; ventilation does not replace air-sealing/insulation.

Code & warranty notes#

  • Many U.S. jurisdictions accept 1:300 (reduced from 1:150 if specific air/vapor conditions are met). Check your local adoption.
  • Some shingle manufacturers require intake/exhaust balance for warranty.
  • In HVL/TAS regions (high wind), use wind-tested vents and corrosion-resistant fasteners.

Cost & labor (ballpark)#

  • Cutting ridge slot + installing baffles: $12–$25 per linear foot depending on access.
  • Typical retrofit time: half-day to two days.